Swiss Rotors Academy – Episode 1: Principles of Fan Operation

Swiss Rotors Academy – Episode 1: Principles of Fan Operation

Today we are launching the Swiss Rotors Academy – a new video series in which our engineers share the practical knowledge behind air handling technology. No marketing slides, no shortcuts: just the physics, the numbers and the experience we use every day when designing EC fans, energy recovery wheels and heat exchangers.

The episode 1 is presented by Cyprian Estemberg, Product Manager at Swiss Rotors. The episodes are recorded at our manufacturing facility in Dębogórze, Poland – the same place where our EC fans are built and tested.

Episode 1: External Pressure ≠ Fan Pressure: How to Calculate What Your AHU Fan Needs 

To understand how a fan works, you first have to understand where it works. In the first episode, Cyprian starts with the ventilation system of a building and follows the air step by step – from the intake, through the Air Handling Unit, to the grille in the room.

Using a simple supply unit as an example, the episode explains:

  • What external pressure really is – the flow resistance of the ductwork only, the figure given by the consultant when the AHU is specified.
  • Where the pressure drops come from – primary filter, cooling coil, heating coil and final filter, each adding its own resistance inside the unit.
  • How static pressure changes across the system – from negative pressure upstream of the fan to positive pressure downstream, with the fan as the boundary between the two.
  • Why the fan has to deliver much more than the external pressure – in the example, 400 Pa of external pressure becomes a static pressure increase of 1,100 Pa that the fan must cover.

From pascals to kilowatts

The second part of the episode goes one level deeper. Multiply the volumetric airflow by the static pressure increase, reduce the units to the SI basics – and the result is expressed in watts.

This is the useful power of the fan: the pure power the fan delivers to the ventilation system. For 10,000 m³/h and 1,100 Pa, that is approximately 3.05 kW.

And then comes the question every HVAC engineer should be able to answer: what happens when a fan spins freely on a table, or runs inside a completely sealed box? It consumes electricity in both cases – but how much useful power does it deliver? Watch the episode to find out.

Why we are doing this

Every Swiss Rotors product starts with the same fundamentals: airflow, pressure, power and efficiency. Understanding them is what allows AHU manufacturers, designers and partners to make better decisions – from fan selection to the energy performance of the entire unit.

With the HVAC Academy, we want to share that knowledge openly with our partners.

Watch the full episode

▶ Watch Episode 1 on YouTube

Subscribe to the Swiss Rotors channel so you don't miss the next episodes of the HVAC Academy.

Engineering knowledge. Explained by the people who build it.